Fire Alarm Control Panel
Fire alarm indication
At the top area of the panel is the main display. When enter to fire alarm, the red FIRE LED lights. If the outputs:
Sounder/ Fire protection/ Fire routing did not disabled or have any faults, red ACTIVE LED light.
Zone Fire Alarm Control Panel Specification
- It is modularized design, the panel can expend from 1 zone to 32 zones easily.
- It has 2 level control mode by a lock
- It has 24VDC and 5VDC power supply output.
- It has FIRE and FAULT signal output.
- It has 2 general sounders output.
- Each zone has 1 circuit detectors input
- Each zone can be disable by a button.
- It has RESET button to reset the panel.
- It has SILENCE button to stop BUZZER and SOUNDERS.
- It has EVACUATE button to start a manual fire alarm immediately.
- It has battery low protection function, when battery voltage lower than 21VDC
battery will be cut off automatically until the mains power is on.
- It has an optional GSM module for fire alarm by SMS
Technical Specifications
AC INPUT | 220VAC 50Hz | +10% |
-15% | ||
DC OUTPUT | 24VDC typical |
Batteries current | 1.85A maximum, current limited | |
Auxiliary output | 24VDC ± 10%, 100 mA max, current limited, monitored |
|
Batteries | 2*12V/ 2.3Ah sealed lead acid gel, self-regulated |